Techno-economic design and optimisation of a hybrid PV–CSP solar power plant in northern Chile

Location
Atacama Desert, Antofagasta Region, Chile
Skills & services
Energy modelling · Feasibility study · Thermal storage sizing · Techno-economic optimisation · PPA and cash flow modelling
estimated annual electricity generation
802.75 GWh
of output in the evening peak, above the 30% tender requirement
31.75%
per MWh optimised base contract (PPA) price
$65.94

How we worked

The project in 5 steps

Step 1 of 5

A tender for dispatchable solar in the Atacama

The tender called for a hybrid plant that delivers clean power when the grid needs it most, not only at midday. The design had to respect a 100 MW export limit and deliver at least 30% of its energy in the evening peak.

Export limit
100 MW
Evening peak target
30% or more
Peak window
17:00 to 24:00

Solar power is cheap at midday but cannot serve the evening peak on its own. We designed and optimised a hybrid plant that pairs PV with concentrated solar power and molten-salt storage, so it delivers firm, dispatchable power when the grid needs it most.

Why hybrid solar matters

Solar power is inexpensive during sunny hours, yet it cannot supply evening and overnight demand on its own. In regions with strong solar resources and shifting daily price profiles, relying only on daytime generation leaves valuable evening and night hours underserved.

Pairing solar photovoltaics with concentrated solar power and thermal energy storage bridges the gap between sunny afternoons and high-demand periods, combining low daytime generation costs with controllable dispatch when the grid needs power most.

System architecture and storage

The modelled facility combines solar PV with concentrated solar power and thermal energy storage reaching up to 565 °C. Surplus energy captured during hours of high availability is stored as heat, ready for later use.

Thermal storage decouples energy capture from delivery. Instead of wasting surplus solar potential or depending only on daytime output, the plant releases stored energy gradually when market conditions and grid needs are more favourable. Move through the day below to see how the plant operates.

Swipe sideways to see the whole plant.

Hybrid PV and CSP plant energy flowsHeliostats heat salt in the tower and store it in the hot tank; PV supplies the grid and an electric heater; the power block draws on stored heat to supply the grid.Heliostat fieldMirrors track the sunSolar towerHeats salt to 565 °CPV array150 MWElectric heaterSurplus PV to heatGrid100 MW limitPower block100 MWe turbineMolten salt storage, 13.5 hCold tankHot tank
12:00
Operating mode
Charging storage
To grid
100 MW
From PV / storage
100 / 0 MW
Hot tank level
82%

Illustrative day based on the optimised design (150 MW PV, 100 MWe CSP, 13.5 h storage, 100 MW export limit). It shows how the plant operates, not hourly model output.

Move through the day to see how sunlight, storage and the turbine share the 100 MW export limit.

Dispatch logic and grid value

An hourly dispatch model evaluates generation, storage levels and time-of-day price signals. Based on those conditions, it decides whether to send power directly to the grid, charge thermal storage, or draw from storage to support evening and night delivery.

Directing output toward evening peaks and higher-price intervals strengthens revenue while supporting steadier grid supply. Consistent delivery across consecutive hours also unlocks additional remuneration for sustained output, making the timing and stability of dispatch central to commercial value.

Design optimisation and validation

To find a well-balanced configuration, the study explored combinations of solar multiple, generation capacity, storage duration and system sizing across two parametric stages. An initial broad sweep narrowed the search space before a finer sweep refined the preferred setup using SAM and Excel VBA automation.

Pareto front analysis weighed upfront investment against electricity cost and contract pricing, while a cross-check against MOSES confirmed overall technical alignment. Comparing the models also showed how operational limits, such as ramp rates and minimum output thresholds, shape real-world performance and highlight areas for deeper engineering review.